Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/26/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The plumbing supply riser does not appear to show the circulating hot water loop (i.e. the hot water source) being within 24-inches of the lavatory stop valves. Revise the riser diagram to show the loop dropping down in the wall so that the ½-inch hot water branches to the lavatories are no longer than 24-inches. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (i.e. 24-inches for ½-inch pipe).] |