Permit Number: T21CM04983
Parcel: 10709031A

Address:
2501 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04983
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1; Foundation Details: Please indicate the detail cuts for the foundation on the Foundation Plan (Sheet 2).
2. Sheet 1; Code Analysis: The new addition will add occupants to the total occupant load. Please provide information on this sheet for the existing occupant load, the new occupant load, the total occupant load, the total required plumbing fixtures, and the total plumbing fixtures provided.
3. Sheets 1 and 3; Framing Details: Please indicate the detail cuts for the roof on the Roof Framing Plan (Sheet 3).
4. General: Please provide structural calculations for the new building addition and the new roof over the existing porch.
5. General: Please provide written responses to all review comments.
06/30/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacity of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
3. Show that the specified heat pump for the addition complies with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018.
4. Show the size, routing, and termination of the condensate drain for the new AC unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
5. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
06/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify how storm water will be drained from the existing building and the new porch Reference: Sections 1101, 1106 and 1108, IPC 2018.
2. Provide sizing information for the roof scuppers on the south side of the addition. Reference: Sections 1106.5 and 1108.3, IPC 2018.
3. Provide secondary (overflow) roof drainage (note: an opening in the collector box is not a secondary drain). Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
06/30/2021 ROBERT SHERRY WATER REVIEW Completed
07/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide complete electrical plans sealed by an Electrical Engineer registered in the State of Arizona.

Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code.

Provide compliance with the 2018 IECC for the lighting.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements
07/14/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/14/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM04983
2501 N Oracle Rd
Building Addition

TRANSMITTAL: July 14, 2021
This site is located in the C-2 zone (UDC 4.7.21).

1. As you are proposing an building addition to the site a Development Package (DP) is required to be submitted and approved prior to approval of this building plan. At a minimum the DP will need to meet the requirements of the Checklist for Minor Changes to Commercial/Industrial Site found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal from the building plan and shall be submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type”, “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/14/2021 JPEELDA1 FIRE REVIEW Approved
07/14/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review