Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM04978
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cleanouts for all horizontal drains; the cleanouts shall not be located greater than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018 2. Revise the design of the sanitary building drain so that no fixtures located above the rim elevation of the next upstream manhole (i.e. those on the 2nd floor) discharge through the backwater valve. Reference: Section 714.1, IPC 2018. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |