Permit Number: T21CM04978
Parcel: 11706166B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04978
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide cleanouts for all horizontal drains; the cleanouts shall not be located greater than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018
2. Revise the design of the sanitary building drain so that no fixtures located above the rim elevation of the next upstream manhole (i.e. those on the 2nd floor) discharge through the backwater valve. Reference: Section 714.1, IPC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2021 NGARCIA3 OUT TO CUSTOMER Completed