Permit Number: T21CM04971
Parcel: 106090110

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM04971
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide complete electrical plans designed and sealed by a Engineer registered in the State of Arizona.

What do you mean by 14/2 wire? If you meant 14 AWG, it must be protected by a 15 amp OCPD not 20. NEC 310.15. Please clarify.

Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code.... See section 104 for plan/permit submittal requirements. Provide plans with the necessary information to verify Outdoor Lighting Code compliance.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2021 NGARCIA3 OUT TO CUSTOMER Completed