Permit Number: T21CM04965
Parcel: 133090430

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04965
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04965

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Clarify items proposed for permit. Remove "existing" from proposed rooms or features built without permit.

Sample drawings are shown as an example: https://www.tucsonaz.gov/pdsd/residential-permits

FLOOR PLAN:

Provide a floor plan showing each room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH.

FRAMING PLAN:

Provide a proposed roof framing plan showing beam, rafter and header locations and sizes.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and anchor bolt size. Show rating of insulation both walls and ceiling. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade.

Provide the placement of ceiling/roof insulation. This determines the need for attic ventilation or the need for an air-impermeable layer if insulation at the roof sheathing.

PLUMBING PLANS:

Provide proposed piping details showing code compliant materials and sizes.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes. Provie a Manual J report identifying cooling demand.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

OUTDOOR LIGHTING CODE

Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
12/17/2021 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T21CM04965
7858 E Fairmount St
Renovate carport into storage, enlarge kitchen, bedroom and bathroom additions (2nd Review)

TRANSMITTAL DATE: December 17, 2021

This site is located in the RX-1 zone (UDC 4.7.6). A single-family residence is a permitted use in this zone (Table 4.8-1) subject to Use Specific Standards 4.9.7.B.6, .8, & .9.

COMMENTS: the minimum required setback to the rear property line is twenty (20) feet (Table 6.3-1.A).
1. The proposed perimeter yard setback from the proposed storage structure to the rear perimeter yard property line is 4'-0". This setback reduction can be alleviated with a neighbor's setback waiver. To secure this waiver, the following text shall be provided on the plot plan and be signed and dated by the adjacent property owner to the south. Provide the following text on the plot plan:

My name is _________ and I am the owner of the property located at _________. I have reviewed the site plan and I have no objection to the structure being located or constructed _____ feet from the property line as depicted on the site plan.

Signature: _________

Date: _________

2. Please clarify that the existing unpermitted studio and the existing unpermitted bathroom addition are included within the scope of work, all as shown on the submitted plans.

If you are unable to secure the neighbor setback waiver a Design Development Option (DDO) will be required. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at (520)837-4951.