Permit Number: T21CM04957
Parcel: 11451142A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04957
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet DP1; General Notes: Note 5 indicates this is an existing retail (M) space. Please revise that occupancy classification to a restaurant (A-2), as this is the function of the space from which the occupant load is calculated (Table 1004.5).
2. Sheet DP1; Outdoor Seating Plan: Please indicate the existing occupant load for the outdoor seating area, the existing area for the outdoor seating area, the new occupant load for the outdoor seating area, the new area for the outdoor seating area, the total area of the existing and new outdoor seating areas, and the total occupant load of the existing and new outdoor seating areas.
3. Sheet DP1; Outdoor Seating Plan: It appears there is only one exit for the total outdoor patio area. If the total patio occupant load is greater than 49, two exits are required. Please verify.
4. Sheet DP1: The plumbing fixtures required for this project should include the total occupant load for the outdoor seating + the indoor occupant load. Please indicate a required plumbing fixture summary for this tenant.
5. General: A new C of O for this restaurant will be required due to the addition of the outdoor seating addition. Please provide all information required.
6. General: Please provide written responses to all review comments.
07/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/13/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/13/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM04957
8987 E Tanque Verde Rd, St. 335
Expansion of Outdoor Seating – C-2

TRANSMITTAL: July 13, 2021

This site is located in the C-2 zone (UDC 4.7.21). Food Service is a permitted use in this zone (Table 4.8-4). See Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. As you are proposing and expansion of use area, outdoor seating, a Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites must be submitted and approved. The checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.
2. A DP is a separate submittal from the building permit and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type”, “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/14/2021 JPEELDA1 FIRE REVIEW Reqs Change Show the existing occupant load and the new occupant load combined. Shows that a fence is being added around the area, if occupant load exceeds 50 you shall add another exit from the patio.

Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2021 VVERA1 OUT TO CUSTOMER Completed