Permit Number: T21CM04953
Parcel: 21248069E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04953
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The COMcheck envelope compliance certificate has been revised to show both R-38 continuous insulation for the roof and R-38 cavity insulation for the roof. Nothing has been changed on the plans to indicate the existence of either type of roof insulation. [Third comment: The conditioned portion of the building envelope has to be altered to fully comply with the energy code. Show how the roof has been provided with R-38 continuous insulation [Second comment: The COMcheck analysis of the IT room appears to be incomplete. The space has both a roof and an entrance door. Revise the COMcheck envelope compliance to show that the space meets the requirements of the current code.] [Initial comment: The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C503.2, IECC 2018 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, IECC 2018.]