Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T21CM04953
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/29/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C503.2, IECC 2018 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, IECC 2018. 2. Provide locking access port caps for the condensing unit per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space. |
| 06/29/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/29/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Please show the Emergency Shut Off for the tanks Include manufacturer cut sheets of the tanks, dispenser containment, dispensers, and piping and UL listings Is the masonry wall engineered for vehicle impact protection? Primary vents are required to be run 12' above grade Plans shall also be submitted to TFD for an operational permit for tanks. If you have any questions please call or email me. Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 07/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Submitted Outdoor Lighting Compliance. The exterior lighting at the fuel storage area does not qualify for the Special area exemption 701.3 per definition. Please provide complete Outdoor Lighting Code Compliance as required per section 104 (Exterior Lighting Plan Submittal Requirements) for the ‘Z2’ luminaires. The ‘Z1’ under canopy luminaire are exempt as stated. Provide a note on the plans for wiring methods in hazardous areas are to comply with NEC 514 and 515 articles. Provide a Grounding Electrode System at the Fuel Facility Structure as required per NEC 250.32. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), City of Tucson Commercial Plan Submittal Requirements |
| 07/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 07/13/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/13/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |