Permit Number: T21CM04953
Parcel: 21248069E

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM04953
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/29/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C503.2, IECC 2018 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, IECC 2018.
2. Provide locking access port caps for the condensing unit per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space.
06/29/2021 ROBERT SHERRY WATER REVIEW Completed
06/29/2021 JPEELDA1 FIRE REVIEW Reqs Change Please show the Emergency Shut Off for the tanks
Include manufacturer cut sheets of the tanks, dispenser containment, dispensers, and piping and UL listings
Is the masonry wall engineered for vehicle impact protection?
Primary vents are required to be run 12' above grade
Plans shall also be submitted to TFD for an operational permit for tanks.

If you have any questions please call or email me.
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
07/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Ref; Submitted Outdoor Lighting Compliance. The exterior lighting at the fuel storage area does not qualify for the Special area exemption 701.3 per definition. Please provide complete Outdoor Lighting Code Compliance as required per section 104 (Exterior Lighting Plan Submittal Requirements) for the ‘Z2’ luminaires. The ‘Z1’ under canopy luminaire are exempt as stated.

Provide a note on the plans for wiring methods in hazardous areas are to comply with NEC 514 and 515 articles.

Provide a Grounding Electrode System at the Fuel Facility Structure as required per NEC 250.32.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements
07/13/2021 STEVE SHIELDS ZONING REVIEW Passed
07/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/13/2021 SSHIELD1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2021 NGARCIA3 OUT TO CUSTOMER Completed