Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM04952
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/23/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/29/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the developed pipe length shown for the existing pizza oven in the gas diagram, A/P1. Reference: Section 107.2.1, IBC 2018. 2. Verify the new appliances being installed. The specified appliance #31 is a unit with 6-burners, a 24” griddle and two ovens; it has a total gas load of 294,000 BTUH per the manufacturer. Appliance #32 is listed as “NOT USED” in the equipment schedule on sheet A3. Reference: Section 107.2.1, IBC 2018. 3. Provide an automatic fuel shut off valve for the Type I hood, interlocked with the hood fire extinguishing system. Reference: Section 904.3.3, IBC 2018. 4. Verify the location of the natural gas meter. The plumbing floor plan appears to show it located within an adjacent suite. Reference: Section 107.2.1, IBC 2018. |
06/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the developed pipe length shown for the existing pizza oven in the gas diagram, A/P1. Reference: Section 107.2.1, IBC 2018. 2. Provide an automatic fuel shut off valve for the Type I hood, interlocked with the hood fire extinguishing system. Reference: Section 904.3.3, IBC 2018. 3. Verify the location of the natural gas meter. The plumbing floor plan appears to show it located within the adjacent suite. Reference: Section 107.2.1, IBC 2018. |
06/29/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
06/29/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/09/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
07/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/13/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |