Permit Number: T21CM04863
Parcel: 13314227C

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM04863
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Is the new switchgear replacement like for like? If yes, please indicate this on the plans. If not, provide a complete line diagram including old and new equipment and grounding details, OCPD’s, GFI protection, Voltage, Phase, Amps, AIC, etc.

Indicate on the plan if there is any change in load. If yes, provide complete load calculations.

Identify the old and new switchgear on the electrical floorplan.

Identify the temporary 500kw generator on the electrical floorplan as mentioned in the CONSTUCTION PHASING notes and provide more details for the temporary conductors, grounding and terminations.

Where is generator #1? Is this a new generator on the new generator pad per KEYNOTE #6. Provide detailed information for the new generator (Ratings), feeders, OCPD’s , voltage, phase, etc.

Provide information addressing any changes for the Generator and Switchgear grounding .

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2021 NGARCIA3 OUT TO CUSTOMER Completed