Permit Number: T21CM04846
Parcel: 137055810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04846
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that this area is actually an S-2 occupancy and not an S-1 Occupancy. Reference: Section 311.2, IBC 2018.
2. Provide the quantity of combustible materials stored or mixed in the control area. Reference: Sections 502.9.5.2 and 502.9.4, IMC 2018.
3. Provide make-up air for the to offset the hood exhaust. Reference: Section 502.9.4, IMC 2018.
07/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The OCPD in panel ‘B’ shown for panel ‘F’ is 3 phase type and your showing a 3 phase panel ‘B’, but the panel schedule shows 1 phase. New panel ‘F’ schedule also shows 1 phase and the feeder should be 4 current carrying conductors and a ground if its 3 phase. Also the lettering shown on the panel schedule is overlapping (WIRE MAIN). Please clarify and revise the plans.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
07/13/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/13/2021 STEVE SHIELDS ZONING REVIEW Approved
07/14/2021 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2021 VVERA1 OUT TO CUSTOMER Completed