Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM04846
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/24/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that this area is actually an S-2 occupancy and not an S-1 Occupancy. Reference: Section 311.2, IBC 2018. 2. Provide the quantity of combustible materials stored or mixed in the control area. Reference: Sections 502.9.5.2 and 502.9.4, IMC 2018. 3. Provide make-up air for the to offset the hood exhaust. Reference: Section 502.9.4, IMC 2018. |
07/07/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The OCPD in panel ‘B’ shown for panel ‘F’ is 3 phase type and your showing a 3 phase panel ‘B’, but the panel schedule shows 1 phase. New panel ‘F’ schedule also shows 1 phase and the feeder should be 4 current carrying conductors and a ground if its 3 phase. Also the lettering shown on the panel schedule is overlapping (WIRE MAIN). Please clarify and revise the plans. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
07/13/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
07/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/14/2021 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/14/2021 | VVERA1 | OUT TO CUSTOMER | Completed |