Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04844
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Interior waste piping upstream of the grease interceptor shall have a minimum slope of ¼” per foot (2% slope). Reference: Section 704.1, IPC 2018. 2. Revise the vent protecting the grease interceptor. All vents (except for vents serving interceptors located outdoors) shall rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. |