Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04812

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved



BUILDING REVIEW COMMENTS:
Denied
1. The walk-in cooler door swings into the path egress more the permitted allowance. Provide a corrected door swing that is in accordance with Section 1005.7.1.
2. It appears the the wire shelving (44C), that is adjacent to the walk in cooler, protrudes into the path of egress that may reduce it beyond the permitted allowance. Provide clarification or evidence of compliance with Section 1005.7.3.


MECHANICAL REVIEW COMMENTS:
Approved



ELECTRICAL REVIEW COMMENTS
Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2022 VVERA1 OUT TO CUSTOMER Completed