Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM04779
Parcel: Unknown

Address:
3504 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04779
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. Reference: Section 403.2.1 (3), IMC 2018.
2. The addition of the Type I grease hood to the suite has resulted in the suite having 750 CFM more exhaust flow than make up air flow. Show how adequate make-up air is to be provided to the room so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2018.
3. Show that combustible materials (e.g. wood studs) are not located within 18” of the Type I hood. Reference: Section 507.2.6, IMC 2018.
06/15/2021 ROBERT SHERRY WATER REVIEW Completed
06/16/2021 JPEELDA1 FIRE REVIEW Approved
06/23/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review: The Code Review indicates this is a retail occupancy group with no change from the previous use. From the floor plan on Sheet A3, it appears the majority of this tenant space is for food preparation and food service. The addition of a new hood would support that determination. Please revise the Code Review for an A-2 Occupancy Classification.
2. Sheet A3 (Detail 1); Sheet A6 (Detail 4): Detail 1 indicates a 48" high pony wall, while Detail 4 indicates a 72" high pony wall. Are these different pony walls? Please indicate Detail 4/A6 on the Floor Plan on Sheet A3.
3. Sheet A6; Detail 6: Please provide the screw size at the top and the bottom of the metal stud bracing.
4. General: Please provide written responses to all review comments.
07/06/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/12/2021 STEVE SHIELDS ZONING REVIEW Approved
07/12/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed