Permit Number: T21CM04727
Parcel: 140260090

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04727
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The grease interceptor sizing calculations show a required 100 GPM flowrate, but only a 75 GPM interceptor is existing. How is this adequate? [Initial comment: Provide the capacity of the existing grease interceptor and verify that it meets the needs of the connected fixtures. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
07/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed