Permit Number: T21CM04720
Parcel: 12621002A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM04720
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/22/2021 IMONSHI1 NPPO REVIEW Passed
06/30/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04720

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

FRAMING PLAN:

Provide truss plans and header locations and sizes.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and anchor bolt size. Show rating of insulation both walls and ceiling. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade.

Provide the attic ventilation opening sizes and locations.

Show an air-impermeable layer if insulation at the roof sheathing in areas without attic ventilation.

PLUMBING PLANS:

Show the location of the tankless water heater with appropriate gas pipe size..

MECHANICAL PLANS:

Provie a Manual J report identifying cooling demand.

ELECTRICAL PLANS:

Provide a cardon monoxide detector location if the dwelling has a natural gas appliance.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/30/2021 IMONSHI1 ZONING REVIEW Approved
07/14/2021 JPEELDA1 FIRE REVIEW Approved