Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM04699
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM04699 6990 E 39th PL Extend Living Room TRANSMITTAL DATE: June 9, 2021 This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5-.9. 1. Please add the following to the residential plot plan that meets all requirements shown at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. a. Please provide the zoning of the property, including all the surrounding zoning of adjacent sites. b. Add a legal description c. Add a lot coverage calculation d. Provide the owner's name e. Show all easements of record on the property f. Show the location of the nearest fire hydrant g. Show the height of the proposed structure on every side. h. Provide setback measurements for the entire site Refer to the second page of the template posted above as a checklist. If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov |
| 06/09/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 06/09/2021 | NMARTEL1 | NPPO | REVIEW | Passed | |
| 06/29/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T21CM04699 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place each plan sheet into a single PDF file for reviewing as a complete plan set. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits Or by request at PDSD-Residential@tucsonaz.gov SITE PLAN: Provide a site plan showing all buildings, R106.1.1. Show square footage (existing & proposed separately) and setback measurements to property lines and location of utility lines to the building. FLOOR PLAN: Provide a floor plan showing each room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window opening into the proposed space. FRAMING PLAN: Provide a roof framing plan showing beam, rafter and header locations and sizes. SECTIONS - DETAILS: Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and anchor bolt size. Show rating of insulation both walls and ceiling. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade. Provide the placement of ceiling/roof insulation. This determines the need for attic ventilation or the need for an air-impermeable layer if insulation at the roof sheathing. PLUMBING PLANS: Provide piping details showing code compliant materials and sizes. MECHANICAL PLANS: Provide equipment details showing code compliant components, locations and sizes. Provie a Manual J report identifying cooling demand. ELECTRICAL PLANS: Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection. INTERNATIONAL ENERGY CONSERVATION CODE: Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better. OUTDOOR LIGHTING CODE Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly). If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |