Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

The revised electrical plan still does not satisfy the previous electrical review comment completely. Reference; Plan EM1, KEYNOTE #8 calls out a single 120volt, 30 amp Washer/Dryer outlet, and the electrical floorplan shows it on Branch Circuit #11. Ref; Plan E2. The panel schedule calls out a 240 volt Branch Circuit on Circuits #11, #13.. Please clarify.. Also provide the correct symbol for the Washer/Dryer outlet(s) when the correct configuration is determined.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.