Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04689
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/11/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/12/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. The revised electrical plan still does not satisfy the previous electrical review comment completely. Reference; Plan EM1, KEYNOTE #8 calls out a single 120volt, 30 amp Washer/Dryer outlet, and the electrical floorplan shows it on Branch Circuit #11. Ref; Plan E2. The panel schedule calls out a 240 volt Branch Circuit on Circuits #11, #13.. Please clarify.. Also provide the correct symbol for the Washer/Dryer outlet(s) when the correct configuration is determined. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |