Permit Number: T21CM04689
Parcel: 115046800

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04689
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a sign stating the equivalent length of the concealed dryer exhaust duct. [Initial comment: Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.8.4.2, IMC 2018.]
07/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change “Ready access” is defined as not “requiring the removal or movement of any panel, door or similar obstruction” to reach a fixture. Reference: Section 202, IPC 2018. [Initial comment: Show that ready access is provided for the indirect waste receptor for the clothes washer. Reference: Sections 202 (Ready Access) and 802.4, IPC 2018.]
07/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments. Also provide a written response.

The electrical floor plan shows individual receptacles 1 for the washer (120volt, 20amp) and then another for the dryer (30amp), also see KEYNOTES #7, #8. The panel schedule shows a 240volt 2-pole circuit breaker for both. Please clarify.

Per KEYNOTE #7. There is no art 250.57b in the NEC. The dryer should be grounded per NEC art 250.140. Equipment Grounding Conductor. Please revise KEYNOTE #7 with the correct Code section.

The washer receptacle requires GFI and ARC Fault protection per NEC art 210.8A, 210.12A.

Ref; 2018 IBC 107.2.1, 2017 NEC.