Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04689
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a sign stating the equivalent length of the concealed dryer exhaust duct. [Initial comment: Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.8.4.2, IMC 2018.] |
| 07/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | “Ready access” is defined as not “requiring the removal or movement of any panel, door or similar obstruction” to reach a fixture. Reference: Section 202, IPC 2018. [Initial comment: Show that ready access is provided for the indirect waste receptor for the clothes washer. Reference: Sections 202 (Ready Access) and 802.4, IPC 2018.] |
| 07/20/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following Electrical plan review comments. Also provide a written response. The electrical floor plan shows individual receptacles 1 for the washer (120volt, 20amp) and then another for the dryer (30amp), also see KEYNOTES #7, #8. The panel schedule shows a 240volt 2-pole circuit breaker for both. Please clarify. Per KEYNOTE #7. There is no art 250.57b in the NEC. The dryer should be grounded per NEC art 250.140. Equipment Grounding Conductor. Please revise KEYNOTE #7 with the correct Code section. The washer receptacle requires GFI and ARC Fault protection per NEC art 210.8A, 210.12A. Ref; 2018 IBC 107.2.1, 2017 NEC. |