Permit Number: T21CM04689
Parcel: 115046800

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04689
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
2. Show that ready access is provided for the indirect waste receptor for the clothes washer. Reference: Sections 202 (Ready Access) and 802.4, IPC 2018.
06/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the clothes dryer vent detail to correspond to the present conditions, i.e. the dryer installation is on an upper floor, not the basement. Reference: Section 107.2.1, IBC 2018.
2. Verify that the termination of the dryer vent is not directed onto a walkway. Reference: Section 501.3., IMC 2018.
3. Show how the dryer installation complies with Section 504.6, IMC 2018.
4. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.8.4.2, IMC 2018.
06/23/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/30/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

It appears there is more proposed electrical work other that the installation of the Washer and Dryer power outlets. Please indicate on the plan what electrical is existing and what is new or relocated.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.