Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM04681
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2021 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T21CM04681 Roof top Solar Panels (1st Review) 3601 S San Rafael PL TRANSMITTAL DATE: June 12, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. o COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. o COMMENT: This plan set is not compliant with 2018 International Fire code, Provide compliance to 2018 International Fire Code 1204.2.1.1. "If the slope of the building is greater than 2:12 must demonstrate compliance with the 2018 International Fire Code 1204.2.1.1 showing a 36" wide access pathway from the eave to the ridge on both sides of the building" o COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/12/2021 | VVERA1 | OUT TO CUSTOMER | Completed |