Permit Number: T21CM04643
Parcel: 116206290

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM04643
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Correct the ventilation calculations. Vbz = (25.6)(7.5)+(0.12)(1707) = 397, not 317. The outdoor air rate for a public corridor is 0.06 CFM/square foot, not 0.03 CFM/square foot. Where did the system population of 37 come from? Reference: Section 403.3.1, IMC 2018.
06/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2021 NGARCIA3 OUT TO CUSTOMER Completed