Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Correct the ventilation calculations. Vbz = (25.6)(7.5)+(0.12)(1707) = 397, not 317. The outdoor air rate for a public corridor is 0.06 CFM/square foot, not 0.03 CFM/square foot. Where did the system population of 37 come from? Reference: Section 403.3.1, IMC 2018.
06/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved