Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Indicate the conduit, conductor, quantity, sizes and types for the feeders between the Meter, service disconnect, and the service disconnect and panel ‘SES2’.

Indicate the size and conductor type for the GEC between the 2 service equipments.

Provide a number or some type of service identification for the services. #1 and #2, or A and B. Correlate with Pima County Addressing for assignment. Also show the locations on the site plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2021 NGARCIA3 OUT TO CUSTOMER Completed