Permit Number: T21CM04607
Parcel: 131030250

Address:
5218 E 23RD ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM04607
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/15/2021 LSHAMIS1 ZONING REVIEW Approved
06/28/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04607
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of the water line from property line (meter) to building, R106.1.1. Show an existing or upgraded 1” line to the building. Minimum size for a two bathroom building is usually 1”, P2903.7.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1. Upgrade the GLB to 5-1/8”x10-1/2” or similar for live and dead loads with a 15.5’ span.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16. Add ARC to the notation.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Both standard and high density batt insulation requires a space greater than provided with 2” x 6” framing, N1102.1. Identify the products that provide the intended minimum R-30 total value with a 2-layer batt and ridge board system or closed cell foam, R806.5.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/28/2021 AWARNER1 NPPO REVIEW Passed