Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 PCAMARE1 OIP REVIEW Completed FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM04603
Roof top Solar Panels
2321 E Hedrick Rd

TRANSMITTAL DATE: January 10, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Please provide the slope of the roofs. If slope is getter than 2:12 compliance with 2018 International Fire Code 1204.2.1.1. must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building.


COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.