09/08/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM04603
Roof top Solar Panels (1st Review)
2321 E Hedrick Dr

TRANSMITTAL DATE: September 8, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


? COMMENT: The planset shows a line-side tap, Line taps require compliance with NEC 230.46 and maintain UL listing. Update the plans showing a tap enclosure with sufficient space for the tap device.

.
? COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans