01/31/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Attic ventilation is not appropriate with insulation placed at the roof sheathing as shown on A.5, R806.1. Remove roof vent calcs from A.7.

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.