Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM04554
Parcel: 133291130

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM04554
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Attic ventilation is not appropriate with insulation placed at the roof sheathing as shown on A.5, R806.1. Remove roof vent calcs from A.7.

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.
02/01/2022 NMARTEL1 ZONING REVIEW Approved
02/25/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2022 NGARCIA3 OUT TO CUSTOMER Completed