Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04554
Parcel: 133291130

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM04554
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/14/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T21CM04554 (Project Number)
SFR Addition/remodel (1st Review)
8411 E Appomattox St

TRANSMITTAL DATE: June 14, 2021

DUE DATE: June 16, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The proposed use is single family residential, which is permitted in the R-1 zone, use specific standard 4.9.7.B.5 - 9 are applicable.

02. COMMENT: Provide the height of the new, proposed exterior walls to determine the proposal is meeting the setback standards. The setback standards for R-1 zone are 6’ or 2/3 the height of the adjacent wall, the greater will apply, measured from the exterior wall to the property line. Indicate the direction of the elevation drawings. See UDC, Section 6.4.5 for the rules of measurement for perimeter yard setbacks.

If you have any questions about this transmittal, Contact Loran Shamis at Loran.Shamis@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
06/14/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T21CM04554 (Project Number)
SFR Addition/remodel (1st Review)
8411 E Appomattox St

TRANSMITTAL DATE: June 14, 2021

DUE DATE: June 16, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The proposed use is single family residential, which is permitted in the R-1 zone, use specific standard 4.9.7.B.5 - 9 are applicable.

02. COMMENT: Provide the height of the new, proposed exterior walls to determine the proposal is meeting the setback standards. The setback standards for R-1 zone are 6’ or 2/3 the height of the adjacent wall, the greater will apply, measured from the exterior wall to the property line. Indicate the direction of the elevation drawings. See UDC, Section 6.4.5 for the rules of measurement for perimeter yard setbacks.

If you have any questions about this transmittal, Contact Loran Shamis at Loran.Shamis@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
06/24/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04554
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Remove the return air opening from the bathroom, R1602.2.4.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/28/2021 AWARNER1 NPPO REVIEW Passed