Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM04511
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 06/11/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/11/2021 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 06/23/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T21CM04511 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SECTIONS - DETAILS: 1. Show a cross-section detail of the new exterior wall, R106.1.1. Show the minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. 2. Show frame wall supported with a foundation stem for achieving the 6” clearance between framing and ground (R317.1 item 5) or 2” above a garage floor. 3. Show the weep screed with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Consider a design with concrete stems. 4. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. The space between roof insulation and ceiling may not be vented. 5. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. 6. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |