Permit Number: T21CM04486
Parcel: 12208016B

Address:
4112 E GRANT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM04486
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a copy of the easement to cross parcel 12208016C.
2. Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2021 NGARCIA3 OUT TO CUSTOMER Completed