Permit Number: T21CM04482
Parcel: 133251010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04482
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04482
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

1. Indicate the electric line as Overhead or Underground, R106.1.1.
2. Indicate the location and size of the water line from property line (meter) to building, R106.1.1. Show an existing or upgraded 1” line to the water heater. Minimum size for a pipe supplying two bathrooms within the building is 1”, P2903.7.

FLOOR PLANS:

1. Show a floor plan with each adjacent room with entry to the proposed room or enclosed window, R106.1.1. All bedrooms require an appropriate exterior egress R311.

SECTIONS - DETAILS:

1. Show a cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface (R403.1) with 12” minimum width for wood framed walls R403.1.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-30 when extended over the wall top plate for additions under 500 SF.

MECHANICAL PLANS:

1. Show bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity. .
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. This may require a floor mounted receptacle outlet within 18” of the window wall, R3901.2.3.
3. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/26/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM04482
Residential Addition
July 26, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. Please resubmit the site plan so it is more legible. Zoning accepts hand-drawn plans, but as this will be an official plot plan, please resend the site plan with straight lines and more legible line weight. The following plan found on the assessor's web page may help: https://www.asr.pima.gov/ParcelData/Apex/13325/1010-1.JPG

a. Please add the legal description to the next site plan
b. Please recalculate the lot coverage to include any vehicle use areas.
c. Please label the elevation height on the elevation drawing.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov