Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04471
Parcel: 115060150

Address:
255 W FLORES ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04471
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The outside air schedule calls for 45 CFM of continuous ventilation; scheduling EF-1 for only 20 CFM of continuous exhaust is insufficient. [Initial comment: Provide the sequence of operation for EF-1. Reference: Sections 403.3.2.3 and 403.3.2.4, IMC 2018.]
07/14/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/14/2021 STEVE SHIELDS ZONING REVIEW Approved