Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04471
Parcel: 115060150

Address:
255 W FLORES ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04471
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the sequence of operation for EF-1. Reference: Sections 403.3.2.3 and 403.3.2.4, IMC 2018.
2. Verify that the range hood will exhaust 100 CFM intermittently or 25 CFM continuously. Reference: Section 403.3.2.3, IMC 2018.
06/02/2021 JPEELDA1 FIRE REVIEW Approved
06/02/2021 ROBERT SHERRY WATER REVIEW Completed
06/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/16/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM04471
255 W Flores St.
Apartment Remodel

TRANSMITTAL: June 16, 2021
This site is located in the C-2 zone (UDC 4.7.21). Multifamily is a permitted use in this zone (Table 4.8-4).

1. Based on the provided plan an additional bedroom is being added to this unit as the study qualifies as a bedroom base on UDC Article 11.4.3 DEFINITIONS – B, Bedroom, the term bedroom includes all of the following: 1) Any room that is designated as a bedroom; 2) Any enclosed room that has a minimum area of 60 square feet and has an accessible opening to the exterior of the building in compliance with the International Building Code (IBC), whether termed a studio, family room, study, den, bonus room, or any other name, except for a living room, dining room, kitchen , and bathrooms; and 3) Any room designated as a bedroom for the purpose of any other code requirement. Demonstrate on the plan that the vehicle parking meets the minimum required with the additional bedroom. As this site appears to be nonconforming for vehicle parking the additional bedroom may require full code compliance due to the increase in density.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
06/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/07/2021 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2021 DBENOIT1 APPROVAL SHELF Completed
07/07/2021 DBENOIT1 OUT TO CUSTOMER Completed
07/07/2021 DBENOIT1 REJECT SHELF Completed