Permit Number: T21CM04461
Parcel: 141210270

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04461
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2021 JPEELDA1 FIRE REVIEW Approved
06/09/2021 ROBERT SHERRY WATER REVIEW Completed
06/25/2021 IMONSHI1 ZONING REVIEW Approved
06/25/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04461

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
No Architectural Plan showing the extent and locations of the Canopies is submitted. Structural Drawing Sections are Typical Sections sending the reviewer to Schedule A for the widths. Tee Canopy Schedule on Drawing S1 is for Typical widths of 30 ft, 35 ft, 40 ft and 45 ft. Resubmit with an overall plan showing widths and extent of Canopies which were used for this particular project. This submittal is incomplete and confusing for review.
Structural Calculations have been reviewed and approved.

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E2: Should provide a note to clarify/reference conduit schedule on sheet E5.
E3: Should provide a note to clarify/reference conduit schedule on sheet E5.
E4: Provide short circuit calculation from utility source (transformer) to SES panel. It is a Tucson requirement.
E6: Need to provide exterior lighting comcheck for the outdoor lighting design.

PLUMBING REVIEW COMMENTS:
Approved
06/25/2021 IMONSHI1 ENGINEERING REVIEW Passed
07/13/2021 NROSS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2021 VVERA1 OUT TO CUSTOMER Completed