Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM04453
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a plumbing design for the relocation of one sink and the installation of a new mop sink. Show the location of the hot water source. Reference: Section 107.2.1, IBC 2018. |
| 06/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the notes in the restrooms 106 and 107; to what is the “30 CFM” referring, supply or exhaust? 2. Provide a return for office #2 to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018. |
| 06/02/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 06/14/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Building Codes: Please indicate the issue date of the listed codes. Remove the Residential Code and the Inclusive Home reference. Add the 2009 ICC/ANSI A117.1 Accessibility Code. 2. Sheet A1; Code Review: Under "Public Charter", the occupant load listed is 46 student seats + 3 staff (49 total). The "Occupant Load" calculated indicates 50.36 occupants (51 total). Please coordinate. 3. Sheet A1; Code Review: The travel distance indicates 75' for a non-sprinklered building. This is in reference to the common path of egress travel, or the exit access travel distance when there is only one exit. Per the IBC Table 1017.2, the exit access travel distance for an E occupancy classification with no sprinkler system is 200'. Please revise. 4. Sheet A1; Wall Detail 2: Please indicate the gauge of the metal wall studs in this detail. 5. Sheet A1; Detail 3: Please indicate the new framing and connections for the soffit. 6. Sheet A3; New Floor Plan: Plan Notes at the service sink reference 13 and 14. Please revise those notes to 14 and 15. 7. Sheet A3; Cabinet Elevation A: Per the IBC Section 1109.3 and the ICC/ANSI Figure 606.3, the maximum allowable of the sink/cabinet is 34". Please revise Elevation A to meet that requirement. 8. General: Please provide written responses to all review comments. |
| 06/16/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM04453 7320 E Broadway Blvd Charter School TRANSMITTAL: June 16, 2021 This site is located in the C-1 zone (UDC 4.7.20). Elementary and Secondary Education is a permitted use in this zone (Table 4.8-4). Subject to Use Specific Standards 4.9.3.D.1 - 7 and 4.9.13.O. 1. Demonstrate on the plan that all Use Specific Standards are met. It appears that all but 4.9.3.D.7 are met. Or provide a letter from the Zoning Administrator that provides exempt status from the UDC requirements for this charter school. The Zoning Administrator can be reached at Russlyn.Wells@tucsonaz.gov. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 06/22/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/15/2021 | LSHAMIS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |