Permit Number: T21CM04427
Parcel: 128062170

Address:
6045 E 21ST ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM04427
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM04427
6045 E 21st St
Sleeping Qtrs (1st Review)

TRANSMITTAL DATE: June 9, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

1. Provide a lot coverage that meets requirements of Unified Development Code (UDC) Article 6.4.3 and the example shown on the residential plot plan requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

2. The building setbacks shown on sheet G-1 are not correct. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 Zone, Res Use to Res Zone the required “REAR” & “SIDES” perimeter yard setback is 6’-0” or 2/3 height of the exterior wall, greater of the two.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
06/22/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM04427
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the utility service for verifying correct sizes and necessary upgrades.

PLUMBING PLANS:

1. Show an individual water heater for the detached dwelling space, P2801.1.
2. Show an individual accessible water supply shut off for the detached dwelling space, P2903.9.1.
3. Provide the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 3/4” service pipe is required for supplying water up to 9.5 fixture units.

MECHANICAL PLANS:

1. Update the code reference to 2018 IRC.
2. Provide an equipment specification list including the (fans, furnace and AC) size or capacity, M1302.1.

ELECTRICAL PLANS:

1. Provide an electrical riser diagram, E3403.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2.
3. Show a Bathroom receptacle on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
Update note #12 with “bedroom” limitation.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 (R-30 for a qualifying room addition) and walls R=13. Show the “R” values of insulation and the maximum “U” factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review