Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM04421
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the additional patio area will not require the installation of additional plumbing fixtures in the suite. Reference: Section 2902.1, IBC 2018. |
| 06/01/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/01/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Please show the existing exiting from the building. Large doors to the patio may be designed as emergency exits and therefore we would need a larger exiting plan from the new pation. Plans shall also show the existing occupant load and the new added occupant load. Occupancy type on plans is a B but I am sure that it is a A-2. This should also be corrected on the drawings If you have any questions please contact me: Jennifer.Peel-Davis@Tucsonaz.gov |
| 06/09/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.0; General Building Summary: Please indicate on this sheet the number of occupants for the patio extension, the total number of occupants for the existing building + the existing patio + the new patio extension, the square footage of the patio extension, the total square footage of the existing building + the existing patio + the patio extension, and the required plumbing fixtures for the total number of occupants for the existing building + the existing patio + the patio extension. 2. Sheet A1.0; Patio Floor Plan: There are two Keynotes 1 indicated in the existing covered patio area. Please remove those notes. 3. Sheet A1.0; Keynotes: Note 2 indicates a new trident pole standard. Please reference Details 4/A1.1 and 5/A1.1 in this note for the trident footing and top of column. 4. Sheet A1.0; Keynotes: Note 6 indicates a relocated light pole. Please reference Detail 3/A1.1 in this note for the light pole footing. 5. Sheet A1.0; Keynotes: Note 10 should indicate slab thickness and reinforcement. Add a detail to these drawings for the slab edge turndown as required. 6. Sheet A1.1; Keynotes: Note 1 should reference a detail that indicates the new masonry wall reinforcement and foundation. 7. Sheet A1.1; Keynotes: Note 5 should indicate the slab thickness and reinforcement. 8. Sheet A1.1; Keynotes: Note 6 should reference a detail that indicates the new stud wall member size, spacing, and how those members are connected at the top and the bottom. In addition, a foundation and reinforcement should be indicated on the detail for the foundation design. 9. Sheet A1.1; Keynotes: Note 6 indicates a new framed wall. Please provide structural calculations for the roof and wall framing, and for the foundation design. 10. General: Please provide a Special Inspections Certificate with Parts A and B completed. Items should include field welding, pilings, and epoxy anchors. 11. General: Please provide written responses to all review comments. |
| 06/16/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/16/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide complete electrical plans for the relocated light pole and installation of the String Lighting. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior luminaires, Pole Luminaires and the String Lighting. See section 104 OLC for plan submittal requirements. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), City of Tucson Commercial Plan Submittal Requirements |
| 06/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM04421 2900 N Swan Rd Patio Expansion TRANSMITTAL: June 16, 2021 This site is located in C-2 zone, (4.7.21). Food service is an allowed use in the zone (Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P. 1. As you are proposing an expansion of use area a development package meeting the requirements of the checklist for Minor Changes to Commercial/Industrial Sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. This is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the Submission Type, Site Review. The building plans cannot be approved until the DP is submitted and approved. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 06/16/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |