Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM04377
Parcel: 132130660

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04377
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2021 JPEELDA1 FIRE REVIEW Approved
08/09/2021 ROBERT SHERRY WATER REVIEW Completed
08/10/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04334, 4376-4378

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Correction complied
2. Provide note in the mechanical schedule that states FCU's 1&2 shut down upon activation of the area smoke detectors in the space, that is being served by those units and provide a supervisory signal to the fire alarm panel (IMC2018,606.4.1)
3.You must use a fire damper here because their is no ceiling radiation damper made that is dynamic rated, they are all static rated and due to the velocity of air coming thru the main supply duct it can not be accepted (IMC2018,304.1)
4. Correction complied
5. Provide ceiling radiation dampers in all supply and return grills in room# 101 & 201 & 108

ELECTRICAL REVIEW COMMENTS
Denied
E5.02 ELECTRICAL ONE-LINE DIAGRAMS:
Line item 11 on all Optional calculation methods call out units as VA. Should be simply A (amperes).
Grounding Conductor sizing table for line item C is undersized for 600 and 800 amp panels.
Many jurisdictions exceed NEC grounding requirements and need Ufer (A) to match or replace Main grounding electrode (C). Confirm current design is in compliance with local code

PLUMBING REVIEW COMMENTS:
Denied
City of Tucson Amendments to the 2018 International Plumbing Code: Appendix B RATES OF RAINFALL FOR VARIOUS CITIES. REVISE appendix by ADDING “Tucson…3.0” under “Arizona”. You are using 1” for your storm drain calculations and you should be using 3.0”. Demonstrate compliance.
1. P4.04
08/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/13/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
BLDG #1 - T21CM04334, BLDG #2 - T21CM04376, BLDG #3 - T21CM04377 & BLDG #4 - T21CM04378
1002 E 36th St.
Multifamily

TRANSMITTAL: August 13, 2021
This site is located in PAD-15. Multifamily is a permitted use.

1. Zoning has reviewed the building plans for compliance with DP21-0078 and although the building plans appear to match the DP until the DP is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/01/2021 SBLOOD1 ENGINEERING REVIEW Approved