Review Details: REVISION - - 1ST
Permit Number - T21CM04376
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2022 | DBENOIT1 | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM4334/4376-4378 New Apartment Buildings GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionaly Approved no mechanical plans to review ELECTRICAL REVIEW COMMENTS Denied Submittal is called out as a deferred submittal. Submittal needs to be signed and sealed. Current submittal might be able to permit as a site plan. Design drawings are defiecient and missing for a building permit. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |