Permit Number: T21CM04375
Parcel: 132166460

Address:
945 E OHIO ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04375
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/26/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the walk-in freezer meets the construction requirements of Section C403.10.2, IECC 2018.
2. Show that the walk-in freezer meets the efficiency requirements of Sections C403.10 and C403.10.2.1, IECC 2018.
05/26/2021 ROBERT SHERRY WATER REVIEW Completed
06/07/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall indicate the following:
1) Code cycle being used and any amendments
2) Deffered submittals ie : fire sprinkler and fire alarm
3) types of items being stored in the cooler
4) Height of racks in the storage case
If you have any questions please call or email me.
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
06/08/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/17/2021 SROGERS2 ENGINEERING REVIEW Passed
06/17/2021 SAMUEL ROGERS ZONING REVIEW Approved
06/17/2021 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed