Permit Number: T21CM04357
Parcel: 12302085A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM04357
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of both the water service meter and the reduced pressure backflow preventer assembly for the water service. Reference: Section 107.2.1, IBC 2018.
06/03/2021 JPEELDA1 FIRE REVIEW Approved
06/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Needs Review Activity Number: T21CM04357

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The edition of ANSI 117.1 is incorrect on the cover page. Correct edition.
2. No egress plan provided. Provide a detailed egress plan.

MECHANICAL REVIEW COMMENTS:
Denied
Table 403.3.1.1 subnote h states that each manicure and pedicure station is required to have a source capture system
capable of exhausting not less than 50 cfm per station that is in compliance with Section 502.20

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
06/11/2021 IMONSHI1 ZONING REVIEW Approved
06/11/2021 IMONSHI1 ENGINEERING REVIEW Passed
07/06/2021 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2021 DBENOIT1 APPROVAL SHELF Completed
07/06/2021 DBENOIT1 OUT TO CUSTOMER Completed
07/06/2021 DBENOIT1 REJECT SHELF Completed