Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/20/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM04306 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied E1.0: Confirm/correct Emergency Wall packs and Exit signs as currently shown to need 40-amp 208V power source from PA: 18, 20 CB. This is not typical. Lighting schedule calls out for 120V power for wall pack. Exit signs provide no information, however, Exit signs typically match lighting (currently shown as 120V). Note E3 requirement for 40-amp CB is still not in agreement with Panel A schedule. E1.1: Light schedules show B fixtures at 120V, but circuits PA:6,8 and PA:10,12 show many B fixture lights at 208V. Circuits for lighting is generally 120V. Please provide a wiring diagram if this is a specialty light. If it is typical lighting, correct drawings. PLUMBING REVIEW COMMENTS: Approved |