Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM04306
Parcel: 130140270

Address:
4140 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04306
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2021 JPEELDA1 FIRE REVIEW Approved
05/26/2021 ROBERT SHERRY WATER REVIEW Completed
06/10/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04306

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The occupant load on the cover page does not match the occupant load on Sheet A3.0. The occupant load on sheet
A3.0 is that accurate calculated load. Please update the cover page along with the plumbing counts and components
of egress if applicable.
2. The med gas room is missing several requirements. Show compliance with Section 427.2.2.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E1.0 ELECTRICAL POWER PLAN, ELECTRICAL NOTES:
Need to provide circuit numbering/identification for electrical equipment/receptacles. Where
circuits/receptacles are existing, note with (E).
Note E3 requirement for 40-amp CB is not in agreement with Panel A schedule.
Should call out conductor size for circuits vs note ‘Wire Size per NEC’ in Panel Schedules.
E1.1 ELECTRICAL LIGHTING PLAN, FIXTURE SCHEDULE:
Need to provide circuit information for new circuits and note when reusing existing circuits.
Need to provide lighting compliance calculations. Can use www.energycodes.gov to comply with IECC
2018.
E2.0 PANEL SCHEDULE, SINGLE LINE DIAGRAM:
Need to provide fault current analysis (due to relocation of panels). Will need Transformer information
from power company, fault current availability and conductor feeds.
Single Line Diagram calls out panels as existing, not relocated. Coordinate whether relocated or
existing. Need to call out conductors for all relocated panels.
Need to provide KAIC rating of relocated panels.
E3.0 DENTAL EQUIPMENT DETAILS: No electrical issues

PLUMBING REVIEW COMMENTS:
Denied
1.      The med gas room is missing several requirements. Show compliance with Section 427.2.2.
06/11/2021 STEVE SHIELDS ZONING REVIEW Approved
06/11/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/06/2021 LOREN MAKUS ENGINEERING REVIEW Passed Engineering report for LOMR shows 100-year discharge contained in Naylor Wash.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2021 VVERA1 OUT TO CUSTOMER Completed