Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04216
Parcel: 13609001B

Address:
11010 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04216
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2021 KKARSEN1 OIP REVIEW Reqs Change T21CM04216 R1
PLAN REVIEW COMMENTS
Plan review for the above referenced structure is completed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code, 2018 International Fire Code, 2017 National Electrical Code and Arizona Revised Statutes. All features were checked to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Make all corrections and revisions and place all plan pages into a single .PDF file.

Field welded connections require special inspections. Identify the certified inspector on a special inspection request form to be included with the final submitted plans, UAC306.1.5.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
• Limit all code references to those recognized by the City of Tucson. Show the 2017 NEC reference on the plans.
• Provide an Arizona Registered Electrical Engineer’s design and sealed plans for verifying the application and sizing of non-prescriptive structural elements of the ground mounted system, R301.1.3 and E3401. Include foundation plans.
NOTES / SPECIFICATIONS
1. Provide manufacturer’s spec sheets showing module and inverter equipment with listings by an Independent Testing Agency, NEC 690.4(D).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review