Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM04200
Parcel: 116206300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04200
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Drawing G0.0 shows a single drinking fountain located outside of the restrooms. Section 410.3, IPC 2018 clearly states that a minimum of two drinking fountains are required, one for people that use a wheelchair and one for standing persons. Alternatively, a drinking fountain with two spouts (one high and one low) is acceptable. [Initial comment: Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.]
08/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved