Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM04199
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Complete the calculations for the minimum required plumbing fixtures shown on sheet G0.0. Provide the basis for the calculations (i.e. area), the trave route and distance to the plumbing fixtures. 2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018. 3. Specify that all proposed owner-supplied plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018. 4. Provide structural calculations and a design for the construction of the storage room deck to verify that the water heater will be safely supported. Reference: Section 301.2, IPC 2018. |
| 05/18/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the exhaust duct will be routed to the roof. Reference: Section 107.2.1, IBC 2018. 2. Note 2 of the outside air calculation shows a required exhaust flowrate of 519.5 CFM but the exhaust fan schedule only calls for an exhaust flowrate of 275 CFM. Provide the correct exhaust flowrate. Reference: Table 403.3.1.1, IMC 2018. |
| 05/18/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 05/18/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.0; Code Review (Amenities): Please indicate the number of drinking fountains provided. 2. Sheet G0.0; Key Plan: Please indicate on this plan the maximum travel distance to the required toilet facilities meets the requirements of the IBC Section 2902.3.3. Indicate those travel distances on the Key Plan. 3. Sheet G0.0; Code Review (Amenities): Please indicate the total number of plumbing fixtures required for this facility (all tenants) is met per the IBC Table 2902.1. This should include the occupants for all tenant/public spaces. 4. Sheet G0.0; Code Review (Amenities): The number of required water closets indicates 2.62, and the number of required lavatories indicates 1.41. Please verify these numbers per the IBC Table 2902.1 and Section 2902.2(3). 5. General: Please provide on the drawings a detail indicating the top of interior walls bracing as required to meet the horizontal resistance per the IBC Section 1607.15. 6. General: Please provide written responses to all review comments. |
| 06/10/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/10/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/10/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. |