Permit Number: T21CM04198
Parcel: 116206300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04198
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/14/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the mechanical plan to indicate that the walk-in cooler is a future item. [Second comment: Comment not addressed. [Initial comment: Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.]
2. Revise the mechanical plan to indicate that the walk-in cooler is a future item. [Second comment: Comment not addressed. [Initial comment: Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.]